Dantherm offers both cross- and counter flow air-to-air heat exchangers.

Heat Exchange - how it worksHeat 01

The two types of Dantherm heat exchangers differ primarily in the fact that the fluids travel perpendicular to one another through the exchanger (cross-flow) or through the exchanger from opposite ends (counter-flow). The units extract heat from ambient air, exchanging it with the internal circuit and thus providing cooling of the warm internal air. All Dantherm heat Exchangers can be installed without powering down the site and the emergency mode of the Heat Exchangers 30 and 50 allows these units to run independently during power outage.

Capacity

When choosing a cooling technology that utilizes ambient air to cool, it is important to understand the concept of delta t (∆t). ∆t = t internal - t ambient. The capacity is stated as e.g. 288 W/K. This means that at a difference in temperature of 1K= 1°C, the cooling capacity is 0,288kW.

Example:
Average ambient temperature: 20°C, desired internal temperature: 25°C = ∆t = 5 (25-20).

Cores of aluminium or plasticHeat 02

The Dantherm Heat Exchangers feature two types of heat exchanger cores of aluminium and plastic, respectively, specially designed and manufactured by Dantherm. The aluminium plate type heat exchange core is a high-quality core capable of dissipating up to 180W°K (100W/F). The twin sheet plastic core ensures benefits such as reduced weight, low noise and high performance.

Plastic core heat exchangers are commonly criticized for low performance and problems with static electricity. The Dantherm high-performance twin sheet plastic core heat exchangers however, have been designed specifically to overcome these challenges. Special care has been put into obtaining higher and smoother air flow, less pressure drop and low velocity change. Internal air paths are designed of rifle tube formed channels that mix air at the wall with air at the center, which gives eminent heat transfer. External air paths are designed for optimal heat transfer still allowing larger particles to pass without clogging the circuit. Finally, the plastic core has been given anti-static treatment, to overcome the problem of static electricity causing build-up of contaminated particles.

Thermosiphone Heat Exchange Solutions

View our selection of energy-saving Thermosiphone Heat Exchange.

ANIMATION:
HEAT EXCHANGER
Animation Heat Exchanger for telecom cabinet cooling Play
Facts:
Heat Exchange

Closed loop cooling
Stepless fan speed control
CFC and refrigerant free
Light-weight plastic core
Filterless design